88A Manual Reset Protector KUOYUH MINI Overcurrent Protector Breaker
88A series equipment manual reset circuit breakers (commonly known as motor overcurrent protectors) are suitable for AC 50/60Hz, rated working voltage to 250Vac, DC 32Vdc, rated current to 3A-20A for additional overload protection in the internal branch circuit of electrical equipment, a key part of the product The temperature sensing protector.
88A series equipment manual reset circuit breakers (commonly known as motor overcurrent protectors) are suitable for AC 50/60Hz, rated working voltage to 250Vac, DC 32Vdc, rated current to 3A-20A for additional overload protection in the internal branch circuit of electrical equipment, a key part of the product The temperature sensing protector. 88 Series Push-to-Reset circuit breaker is a unipolar, single-push reset thermal protector product, used to protect motor equipment.
Product name: 88A series
rating :3A-20A;
(Input Power):125VAC/250VAC/32VDC 50-60Hz;
(Withstand voltage strength):1500VAC/1min;
Leakage current: ≤0.5mA(1500VAC/min,the leaked current is less than≤0.5mA);
(Insulation Resistance):500VDC1Min≥100MΩ;
(Rated short-circuit capacity):125VAC/1000A,250VAC/1000A;
(Rated breaking capacity): 6 times rated current;
(reset): Manual Push Reset;
(Reset Time): Within 60s”;
Tripping characteristics
(The test environment temperature):25℃±3℃;
(200% of Ratcd Currcnt): 5-30s” Seconds Trip;
(150% of Rated Current): Trip within 1 Hour;
(100% of Rated Current): Hold, No Trip ;
Main Technical Parameters
Rated Current | 125/250VAC |
32VDC | |
Rated Voltage | XXA |
Interrupt Capacity | 1000A(UL1077) |
Insulation Resistance | 500VDC 5s″, insulation resistance≥100ΜΩ |
Dielectric Strength | 1500VAC/min |
Reset Time | within 60S |
Reset Type | Manual reset |
Mechanical/Environmental Data
Working temperature: -10℃ to 60℃
Terminal: Quick-connect terminal or solder terminal
Nut: a variety of options, see product appendix and diagram
Terminal temperature rise: rated current <65℃ (ambient temperature is 25℃)
Contact life: >500Cycles at rated current and 125VAC×150%
Table of Environmental Correction Factors
(Derating Factor) | |
-5°C | (3A-4A)×1.2, (5A-30A)×1.12 |
+40°C | (3A-4A)×0.92,(5A-30A)×0.94 |
The time current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping. Please multiply the current brea ker current ratings by the derating factor shown below
Example:
Normal Continuous Current= 10A
Ambient Temperature = 45 °C
Multiplication Factor = 0.85
Recommended Rating=10A/0.85=11.8A
Select the Nea rest Rating = 12A
OVERLOAD | TRIP TIME |
150% | Trip in a hour |
200% | 5.0-30.0 SEC |
300% | 1.2-12.0 SEC |
400% | 0.6-5.0 SEC |
500% | 0.4-2.8 SEC |
600% | 0.3-1.8 SEC |
800% | 0.18-0.9 SEC |
1000% | 0.12-0.7 SEC |
Performance form of the experiment
Max Resistance V.S.Current Rating at 25℃ | Derating Factor | ||
Temperature | Rating Amp | ||
Current Rating in Amp | Max Resistance in ohms | 60℃ | X 0.6 |
3-4Amp | < 0.05 | 50℃ | X 0.7 |
5-6Amp | < 0.04 | 40℃ | X 0.8 |
7-8Amp | < 0.025 | 30℃ | X 0.9 |
9-11Amp | < 0.02 | 25℃ | X 1.0 |
12-13Amp | < 0.01 | 20℃ | X 1.1 |
14-16Amp | < 0.008 | 10℃ | X 1.3 |
17-25Amp | < 0.007 | 0℃ | X 1.5 |
Approval | File No. | Rated Current | Rated Voltage | Standard |
CUL | E155159 | 3-30A | 125/250VAC | UL1077 |
TUV | B140558611005 | 3-30A | 125-250VAC | EN60934 |
32VDC | ||||
CCC | 2011010307520568 | 3-30A | 125/250VAC | GB17001 |